Instrumentation control unarmored-armored cable. HR PVC/ XLPE Insulated, non screen/collective, screen armored/unarmored ST1/ST2/FR/FRLS/ZHFR.
Used in Indoor and outdoor insulation within industrial process plants and for controls power supply between instruments and process equipment.
Unarmored control cable are generally indoor use and armored cable are indoor as well as outdoor, in dry and wet locations, on racks, trays, in conduit,etc. armored cables are suitable for direct burial.
Selection of controls depends on instruments and process equipment, length between control room and process plants, surrounded temperature etc.
CONSTRUCTION
- Conductor:
Annealed Electrolytic Plain/ Tinned Multi stranded copper conductor. - Insulation:
Polyvinyl Chloride (PVC) HR-Grade - Colour code:
2 Core: Red/Black
3 Core: Red/Black/Green
4 Core: Red/Yellow/Blue/Black
5 Core and above: White insulation with numbers for identification - Collective screen (application for control cables with shielding):
Aluminium Mylar tape along with 0.50sq mm drain wire
- Inner sheath:
PVC (Polyvinyl Chloride) black - Armored:
G.I. wire of 0.90mm/1.40mm/4mm X 0.80mm - Outer sheath:
PVC (Polyvinyl Chloride), Type: ST2, FR or FRLS - Voltage Grade:
300V/600V/ 1100V as per requirement of customer.
Technical Data
Temprature range: | -20° C to +70° C(operational) | |
Minimum Bending radius: | 12 x Cable Diameter | |
Outer sheath: | ||
Application: | ||
Limit of Oxygen Index (LOI) | Min:29% ASTM- |
(FR/FRLS) |
Limit of Temperature Index (Flame Temperature [FT]) |
Min 250°C ASTM- |
|
Amount of Halogen Acid Gas | Max: 20°C ASTM- |
|
Smoke Density | Max:58% ASTM |
(FRLS) |
Electrical data at 20° C
Character | Unit | Values | ||||||||
Conductor Size | Nominal | mm² | 0.50 | 0.75 | 1.00 | 1.50 | ||||
Class Of Conductor | Class-2 or Class-5 as per IEC: Standard | |||||||||
Conductor Resistance | Max | Ohm/km | P 39.0 |
T 40.1 |
P 29.6 |
T 26.8 |
P 18.4 |
T 20 |
P 12.20 |
T 12.70 |
Insulation Resistance | Min (BIS:5308) |
Mohm x km |
PVC : 25 | PE : 5000 | ||||||
Test Voltage Core to Core Core to Screen Core to Armored |
– V V V |
– 1000 volt- 3 minutes 1000 volt- 3 minutes 500 volt- 3 minutes |
*P-Plain T-Tinned
Also available as per specification given by consultant/customers
Diameter of cable (under armored, over armored, overall): Depeneding on the specification the detail will be provided at time of data submission.