    • Conductor:
      Annealed Electrolytic Plain/ Tinned Multi stranded copper conductor.
    • Insulation:
      Polyvinyl Chloride (PVC) HR-Grade
    • Colour code:
      2 Core: Red/Black
      3 Core: Red/Black/Green
      4 Core: Red/Yellow/Blue/Black
      5 Core and above: White insulation with numbers for identification
    • Collective screen (application for control cables with shielding):
      Aluminium Mylar tape along with 0.50sq mm drain wire
    • Inner sheath:
      PVC (Polyvinyl Chloride) black
    • Armored:
      G.I. wire of 0.90mm/1.40mm/4mm X 0.80mm
    • Outer sheath:
      PVC (Polyvinyl Chloride), Type: ST2, FR or FRLS
    • Voltage Grade:
      300V/600V/ 1100V as per requirement of customer.

    Technical Data

    Temprature range: -20° C to +70° C(operational)
    Minimum Bending radius: 12 x Cable Diameter
    Outer sheath:
    Application:
    Limit of Oxygen Index (LOI) Min:29%
    ASTM-
    (FR/FRLS)
    Limit of Temperature Index
    (Flame Temperature [FT])
    Min 250°C
    ASTM-
    Amount of Halogen Acid Gas Max: 20°C
    ASTM-
    Smoke Density Max:58%
    ASTM
    (FRLS)

    Electrical data at 20° C

    Character Unit Values
    Conductor Size Nominal mm² 0.50 0.75 1.00 1.50
    Class Of Conductor Class-2 or Class-5 as per IEC: Standard
    Conductor Resistance Max Ohm/km P
    39.0
    T
    40.1
    P
    29.6
    T
    26.8
    P
    18.4
    T
    20
    P
    12.20
    T
    12.70
    Insulation Resistance Min
    (BIS:5308)
    Mohm x
    km
    PVC : 25 PE : 5000
    Test Voltage
    Core to Core
    Core to Screen
    Core to Armored

    V
    V
    V

    1000 volt- 3 minutes
    1000 volt- 3 minutes
    500 volt- 3 minutes

    *P-Plain T-Tinned

    Also available as per specification given by consultant/customers
    Diameter of cable (under armored, over armored, overall): Depeneding on the specification the detail will be provided at time of data submission.